E-10Connecting the cableTwo electronic cables must be connected to the outdoor unit. The connection cord between indoor unit and outdoor unit. The

Strany 3 - Contents

E-11ENGLISHConnecting the cableWiring Diagram of Power CableELBMCCBMCCB3(C)When using ELB for 1 phasePower SupplyElectrical component boxIndoor UnitMa

Strany 4 - A Type:

E-12Connecting the cable (Continued)Wiring Diagram of Connection Cord When connecting cables, you can connect the cables to the electrical part or

Strany 5 - Wire rope

E-13ENGLISHConnecting the refrigerant pipeL1L0HRefrigerant Piping SystemRefrigerant piping system tablePipe length or heightDC30ETTXDC36ETTXDC42ETTXDC

Strany 6 - Outdoor Unit

E-14Connecting up and removing air in the circuitABCDOutdoor unitVacuum pump The designs and shape are subject to change according to the model.The

Strany 7 - Fence or obstacle

E-15ENGLISHCutting/Flaring the pipes1Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder)2If you

Strany 8

E-16Performing leak testsInsulationNo gapNBR(T13.0 or thicker)BA The designs and shape are subject to change according to the model.LEAK TEST WITH N

Strany 9 - Outdoor unit installation

E-17ENGLISHUsing stop valveTo Open the Stop ValveTo Close the Stop Valve1Remove the cap.2Turn the stop valve clockwise by using a hexagonal wrench.3Ti

Strany 10 - Connecting the cable

E-18The outdoor unit is loaded with sufficient R22 refrigerant for 5 metres of piping.If you have used more than "5m", add "Q" of

Strany 11

E-19ENGLISHPump down ProcedurePump down will be carried out when an evaporator is replaced or when the unit is relocated in another area.1Remove the c

Strany 12 - Connecting the Power Terminal

E-2Safety Precautions(Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.)WARNING• Alw

Strany 13 - Refrigerant Piping System

E-20Terminal M4PVC-insulated green/ yellow wireTo grounding screwSteel coreCarbon plastic50cm30cmChecking correct groundingIf the power distribution c

Strany 14

E-21ENGLISHMemo

Strany 16 - Insulation

ENGLISHINSTALLATION MANUALDCETTXDCGTTXESPAÑOLSystem Air Conditioner SE A DB98-30378A(2)This product is not manufactured for Iran. SVC Warranty wil

Strany 17 - Using stop valve

E-3ENGLISHContents Preparation for outdoor unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Deciding on where

Strany 18 - Long pipe application

E-4B Type: DC60GTTX DC72GTTXPreparation for outdoor unit installationThe air conditioner uses R22 refrigerant.A Type: DC30ETTX

Strany 19 - Pump down Procedure

E-5ENGLISHMoving the Outdoor Unit by Wire RopeFasten the outdoor unit by two 8m or longer wire ropes as shown at the figure. To prevent from damage or

Strany 20 - Checking correct grounding

E-6Deciding on where to install the outdoor unitOutdoor Unit The outdoor unit must not be placed on its side or upside down, as the compressor lubr

Strany 21

E-7ENGLISHDeciding on where to install the outdoor unitSpace Requirements for Outdoor UnitWhen installing 1 outdoor unit The space suggested below

Strany 22

E-8Deciding on where to install the outdoor unit (Continued)Unit : mmWhen installing more than 1 outdoor unitThe units must be installed according to

Strany 23 - INSTALLATION

E-9ENGLISHOutdoor unit installationMake a drain outlet around the base for outdoor unit drainage.If the outdoor unit is installed on the roof, y