Connecting the cable
Two electronic cables must be connected to the outdoor unit.
The connection cord between indoor unit and outdoor unit.
The power cable between outdoor unit and auxiliary circuit breaker.
Specially for Russian and European market, before installation, the supply authority should be consulted to
determine the supply system impendance to ensure compliance.
Example of Air Conditioner System
If an outdoor unit is installed in a place in danger of an electric leak or submergence, you must install the ELB.
Power Cable Specifications
The power cable is not supplied with air conditioner.
For power cable, use the grade H07RN-F or H05RN-F materials.
During the unit installation make first refrigerant connections and then electrical connections.
If unit is uninstalled first disconnect electrical cables, then refrigerant connections.
Connect the air conditioner to grounding system before performing the electrical connection.
CAUTION
Type of outdoor unit Outdoor Power supply
power cable MAX. LENGTH
Type GL
MCCB
mm²,wires m A A
A
DC30ETTX
, 220-240V~, 50Hz
2.5/2 < 10m 20 20
DC36ETTX
, 220-240V~, 50Hz
3.5/2 < 10m 20 25
DC42ETTX
, 220-240V~, 50Hz
3.5/2 < 10m 20 25
DC48GTTX
, 380-415V~, 50Hz
2.5/3 < 10m 20 20
B
DC60GTTX
DC72GTTX
, 380-415V~, 50Hz
3.0/3 < 10m 20 20
Indoor Unit
Power cable
Outdoor Unit
Communication cable
Grounding
Power cable
Communication cable
When using ELB for 1 phase
Communication cable
Grounding
Outdoor Unit
Power cable
Indoor Unit
When using ELB for 3 phase