Control Systems
136
9,9,
Building management system
Object Type Support Description
Analog Input
[Indoor temperature], [Lower limit temperature], [Upper limit temperature],
[Electric value after baseline], [Indoor unit usage after baseline],
[Electric value within the period], [Electric value within period], [Indoor unit error code],
[On/Off controller error code], [Interface module error code],
[SIM interface module error code], [DMS2 status], [DMS2 error]
Analog Output
[Set temperature], [Setting lower limit temperature], [Setting upper limit temperature]
Analog Value
Averaging
Binary Input
[Power On/Off Status], [Filter alert status], [Lower limit function toggle status],
[Lower limit function toggle status], [Upper limit function toggle status], [DI]
Binary Output
[Power On/Off control], [Filter reset control], [Setting lower limit function toggle],
[Setting upper limit function toggle], [DO]
Binary Value
Calendar
Command
Device
[DMS2], [A/C Indoor Unit], [ERV], [AHU], [SIM], [On/Off controller],
[Interface module], [DMS2 DI/DO]
Event Enrollment
File
Group
Life Safety Point
Life Safety Zone
Loop
Multi-state Input
[Operation mode status], [Fan speed status], [Air direction status],
[Cooling only/Heating only/Restriction cancellation status],
[Allow/Stop Remote control/Level 1 status]
Multi-state Output
[Control operation mode], [Control Fan speed], [Control air flow direction],
[Setting cooling only/Heating only/Restriction cancellation],
[Control allowing/stopping remote control/level 1]
Multi-state Value
Notification Class
Program
Pulse Converter
Schedule
Trend Log
Access Door
Event Log
Load Control
Structured View
Trend Log Multiple
2. BACnet Gateway
9) Standard object type
MIM-B17N