E-14
Cable tie
LAN cable
Connect
communication
cable
Adapter
Installing the BACnet Gateway (Continued)
Connecting Centralized Controller
1
Unfasten the 2 screws on the bottom of the BACnet
Gateway front cover. Hold the bottom 2 sides of the
BACnet Gateway and push downwards to slide open the
cover.
2 Connect the adapter to the power terminal.
Arrange the adapter as the right figure.
3
Separate 1 terminal block from 5 terminal blocks which
are attached to RS485 communication terminal.
Then, connect interface communication cable (C1, C2) to
the terminal block.(C1A, C2B)
4
Connect LAN cable to the Ethernet terminal of BACnet
Gateway. Then arrange it using cable tie.
5
Fasten the bottom cover of BACnet Gateway and fix it
using 2 screws.
Maximum 16 centralized controllers can be connected
to one BACnet Gateway.
MIM-B17_BACnet Gateway_IM_E 32390-3.indd 14 2011-04-04 오후 3:44:25